Details
Technical data: HBX-DX-IN / HBX-CR-IN
The Inline Vapor Quality Sensor is engineered to accurately measure the flow in refrigeration systems with high efficiency and flexibility. It comes in a straight configuration, available in sizes ranging from 25 mm to 65 mm, and is capable of handling flow in both directions. Its smooth internal design ensures minimal pressure loss, making it a highly efficient choice. Additionally, the sensor can be installed in either horizontal or vertical orientations, offering versatility for different installation setups.Features:
- LED indicators: Provides clear visual indicators for power supply and alarm status.
- Flexible system compatibility: Works with both DX systems and overfeed systems.
- Pipe sizes: Available in pipe sizes ranging from 25 mm to 65 mm.
- Sensors for all types of liquids: Suitable for all common liquids.
- Split design: Simplifies installation and diagnostics; electronic parts can be removed with two screws.
- Easy configuration: Configuration with a PC using HB Tool software.
Applications:

Connection Diagram:
Drawing:
Specifications:
Power supply |
|
Voltage |
24 V AC/DC |
Current consumption |
Max 600 mA |
Electronic connection |
M12, 5 pins |
Output |
|
Analog output |
4-20 mA |
LED indication |
Green, yellow, and red |
Environmental Conditions |
|
Ambient temperature |
-30...+50°C |
Liquid temperature |
-60...+80°C |
Max. pressure |
100 bar |
Degree of protection |
IP65 |
Vibrations |
IEC 60068-2-6 (4g) |
Mechanical Specifications |
|
Material - mechanical parts |
AISI 304 / PTFE |
Material - electronic parts |
Nylon 6 (PA) |
Dimensions |
See drawing |
Approvals |
|
EMC test |
EN 61000-2 |
Cable Specification (Power Supply) |
|
Cable size |
5 m - 5 x 0.34 mm2 |
Cable glands |
PG7 / M8 |
Cable resistance |
500 Ohm/Km |
Configurations |
|
Configuration |
HB Tool |
Tool to be used |
HBX software |
Valve control (Modulating Valve) |
|
Signal to valve |
4-20 mA |
Valve regulation |
PI-regulation |
Valve control (PWM) |
|
Signal to valve |
24V AC/DC |
PWM period |
0-120 s (default 6 s.) |
Valve Control (Stepper motor) |
|
Stepper motor steps |
25-5000 steps |
Stepper motor speed |
2-40 m/s |
Stepper Motor Phase Current |
0-750 mA |
Stepper Motor Holding Current |
0-250 mA |
Cable Specification (Valve Control) |
|
Length |
3 m (118”) |
Cable Size |
3 x 0.75 mm2 |
Cable Glands |
PG7 / M8 |
View more about Inline Vapor Quality Sensor on main site