Inline Vapor Quality Sensor

Inline Vapor Quality Sensor


Specifications
Details

Technical data: HBX-DX-IN / HBX-CR-IN 

The Inline Vapor Quality Sensor is engineered to accurately measure the flow in refrigeration systems with high efficiency and flexibility. It comes in a straight configuration, available in sizes ranging from 25 mm to 65 mm, and is capable of handling flow in both directions. Its smooth internal design ensures minimal pressure loss, making it a highly efficient choice. Additionally, the sensor can be installed in either horizontal or vertical orientations, offering versatility for different installation setups.

Features:

  • LED indicators: Provides clear visual indicators for power supply and alarm status.
  • Flexible system compatibility: Works with both DX systems and overfeed systems.
  • Pipe sizes: Available in pipe sizes ranging from 25 mm to 65 mm.
  • Sensors for all types of liquids: Suitable for all common liquids.
  • Split design: Simplifies installation and diagnostics; electronic parts can be removed with two screws.
  • Easy configuration: Configuration with a PC using HB Tool software.

Applications:


 

Connection Diagram:




 

Drawing:


Specifications:

Power supply

 

Voltage

24 V AC/DC

Current consumption

Max 600 mA

Electronic connection

M12, 5 pins

Output

 

Analog output

4-20 mA

LED indication

Green, yellow, and red

Environmental Conditions

 

Ambient temperature

-30...+50°C

Liquid temperature

-60...+80°C

Max. pressure

100 bar

Degree of protection

IP65

Vibrations

IEC 60068-2-6 (4g)

Mechanical Specifications

 

Material - mechanical parts

AISI 304 / PTFE

Material - electronic parts

Nylon 6 (PA)

Dimensions

See drawing

Approvals

 

EMC test

EN 61000-2

Cable Specification (Power Supply)

 

Cable size

5 m - 5 x 0.34 mm2

Cable glands

PG7 / M8

Cable resistance

500 Ohm/Km

Configurations

 

Configuration

HB Tool

Tool to be used

HBX software

Valve control (Modulating Valve)

 

Signal to valve

4-20 mA

Valve regulation

PI-regulation

Valve control (PWM)

 

Signal to valve

24V AC/DC

PWM period

0-120 s (default 6 s.)

Valve Control (Stepper motor)

 

Stepper motor steps

25-5000 steps

Stepper motor speed

2-40 m/s

Stepper Motor Phase Current

0-750 mA

Stepper Motor Holding Current

0-250 mA

Cable Specification (Valve Control)

 

Length

3 m (118”)

Cable Size

3 x 0.75 mm2

Cable Glands

PG7 / M8


View more about Inline Vapor Quality Sensor on main site