Liquid Level Sensor - CO2, Butane & Propane

Liquid Level Sensor - CO2, Butane & Propane


Specifications
Details

Technical data: HBLC-CO2

The HBLC-CO2 sensor is specifically designed for measuring CO2, Butane, or Propane refrigerant levels in chillers, evaporators, and condensers. The sensor provides an analog 4-20 mA output signal for straightforward integration with monitoring systems.


Features:

  • Liquid temperature range: Operate across a temperature range of -55°C to 145°C (-67°F to 293°F).
  • Pressure tolerance: Rated for pressures up to 150 bar (2175 psi).
  • Power supply: The sensor operates on a 24V DC power supply.
  • LED indicators: Provides clear visual indicators for power supply and alarm status.
  • Split design: Simplifies installation and diagnostics; electronic parts can be removed with two screws.
  • Easy configuration: Configuration with a PC using HB Tool software.


Specifications:

Standard versions

All sensors has an analog output

Sensor with M12 connector



Control Versions

 

  • /C for modulating valve
  • /S for stepper motor
  • /PWM for pulse modulating valve


Drawing:


 
Power supply
Voltage 24 AC/DC + 10%
Energy consumption Max 50 mA
Plug connection M12, 5 pins - DIN 0627
Output
Analog output 4-20 mA
Alarm output PNP/NPN
Alarm contact functiont NO/NC
Environmental conditions
Ambiant temperature -30...+50°C
Refrigerant temperature -55...+30°C
Max. pressure 150 bar
Protection degree IP65
Vibrations IEC 60068-2-6 (4g)
Mechanical specifications
Thread connection 3/4”
Material - liquid parts AISI 304 / PTFE
Material - electronic parts Nylon 6 (PA)
Size Depends on size
Weight Depends on size
Type Angle
Approvals
EMC test EN 61000-2
Indication
LED indication LED 1 x green, 1 x yellow and 1 x red
Accessories
M12 cabel - 5 m HBxC-M12/5 
Cable specification PUR - 5 x 0,34 mm2

View more about Liquid Level Sensor - CO2, Butane & Propane on main site